UPS ZLPOWER
P/NO: RM2K-C – Rack Mount Online UPS
Application:
UPS ZLPOWER True Online (P/No: RM2K-C) Rack mount High frequency online UPS is specially designed for servers, data-center critical network devices, sensitive electronic equipment, telecom, bank, hospital, bureau, traffic, public security, ATM and so on.
Key Features:
v True Online Double Conversion technology with advanced Microprocessor Control.
v PWM Technology with IGBT.
v LED Indicators display Detailed Real-Time UPS Status and parameters.
v Set Output Voltage, Frequency parameter and bypass function on the display.
v Advanced MCU microprocessor control technology, ensure long life reliability.
v Wide input voltage range, Zero transfer time.
v Rack mount 19” design to save space.
v Excellent Protection against over voltage, over load, over current, over charge and so on.
v Input L and N lines reverse wiring detection, Auto start when AC back.
v DC start function, Input PFC revise function.
v Humanization bypass output, can be adjustable.
v Smart RS232 communication with monitoring software.
v Intelligent slot available for AS-400 Dry contact and SNMP card Remote control.
v Strong antijamming capability.
v Available to work with generators.
v Lightning, surge, short circuit, Network/fax/modem surge protection.
v LED/LCD display panel optional.
SPECIFICATIONS:
Model
|
RM2K-C
|
|
|
Technology
|
True Online Double Convertion
|
|
Rated Power
|
VA/W
|
2KVA/1.6kW
|
|
Input
|
Phase
|
Single Phase with Ground
|
|
Nominal Voltage
|
110/115/120Vac or 220/230/240Vac
|
|
Voltage Range
|
60-138VAC or 115 ~ 300VAC
|
|
Frequency Range
|
46 ~ 54Hz(default), user adjustable within 40~60Hz
|
|
Power Factor
|
0.97
|
|
Connection
|
IEC320-10A
|
|
Output
|
Phase
|
Single Phase
|
|
Voltage
|
110/115/120Vac or 220/230/240VAC ± 2%
|
|
Frequency
|
46~54Hz or 50Hz ± 0.2Hz (Line mode)
|
|
56~64Hz or 60Hz ± 0.2Hz (Line mode)
|
|
50Hz ± 0.2Hz ( Battery mode); 60Hz±0.2Hz(Battery mode)
|
|
Waveform
|
Pure Sine Wave
|
|
Overload Capability
|
110%~150% for 30 sec., 150% for 200 ms
|
|
Current Crest Ratio
|
3:1
|
|
Connections
|
Multi perpose Socket or IEC320 -10A * 4
|
|
Bypass
|
Automatic Transfer
|
on overload and UPS failure
|
|
Before UPS Power-on
|
Default “NO”, user adjustable to “YES”
|
|
Voltage Range
|
80~264VAC (Default), user adjustable within 80~286VAC
|
|
Transfer Time
|
0 ms; less than 4 ms from inverter to bypass and vice versa
|
|
LCD/LED indicators
|
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault
|
|
Audible Alarm
|
Bypass, On battery mode, Battery low, Overload, Fault
|
|
Communications
|
RS-232 Serial Interface
|
|
Intelligent Slot;
|
|
OPTIONS: WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC)
|
|
Network Surge Protection
|
RJ45 I/O port available for network or Fax/Modem
|
|
Environmental
|
Operating Temperature
|
0 ~ 40°C
|
|
Operating Humidity
|
20 ~ 90% non-condensing
|
|
Main Unit
|
Net Weight (Kg)
|
8.5 kg UPS (2U)
|
|
Dimensions (L x W x H) mm
|
483 x 467 x 88 (2U)
|
|
Battery Pack
|
Type
|
External Battery Pack
|
|
Nominal DC Voltage
|
96VDC
|
|
Battery Numbers & Capacity
|
8Pcs *12V7.2Ah
|
|
Backup Time (Full load)
|
9 min ( with 1 Battery Pack)
|
|
|
Recharge Time
|
5hrs to 90%
|
|
Charging Current (Max.)
|
1.0A
|
|
Charging Voltage
|
110Vdc±0.4V
|
|
Net Weight (Kg)
|
25.3 kg
|
|
Dimensions (L x W x H) mm
|
483 x 467 x 88 (2U) Battery Pack
|
|
* Product specifications are subject to change without further notice.