APPLICATION:
Three phase High frequency online UPS EX3320K-EX3380K is IGBT rectified uninterruptible power supply 20KVA to 80KVA, Three phase 4line and ground, 0.8 output power factor and DSP chip, is applicable to small and medium-sized data centers, network management center, computer rooms for enterprises, or able to provide solutions to conditions like voltage instantaneous drop-off or damping concussion, high-voltage pulse, voltage pulsation, surge voltage, harmonic distortion, and frequency fluctuation.
Main Features:
*Excellent performance in industrial environment protection
*N+X parallel redundancy up to 6 units (compatible to battery share in the parallel mode)
*Intelligent management of battery charging and discharging
*Frontal-board LCD display panel operation and maintenance
*Twin-channel line input
*Remote monitoring
*High-efficient DSP chip
*Outstanding electric property
*Flexible battery arrangement
TECHNICAL SPECIFICATION
Model
|
EX3340K
|
UPS ZLPOWER EX3340K
|
Rated Capacity
|
40KVA/32KW
|
TECHNOLOGY
|
|
Double conversion online type
|
Input
|
Voltage range
|
210 - 475 VAC
|
Phase
|
Three phase 4 line + each line
|
Frequency
|
40 - 70 Hz
|
THDI
|
< 3%
|
Input power factor
|
>0.99
|
Twin - chanel Line input
|
Yes
|
|
|
Battery
|
Type ZLPOWER
|
Valve-regulated lead-acid storage battery
|
Backup-time full load
|
Depended by external battery bank
|
Output
|
Voltage
|
380VAC / 220 VAC
|
Phase
|
Three phase 4 line + each line
|
Frequency
|
50/60Hz
|
Rate output Power Factor
|
0.8
|
Overload capacity
|
125% maintain 10minutes,150% maintain 1minutes
|
Distortion
|
Linear load <3%, non linear load<5%
|
Bypass
|
|
Automatic transfer
|
Efficiency
|
Line Input mode
|
93%
|
BAT Mode
|
93%
|
ECO Mode
|
98%
|
Intelligent Speed Control of Fan
|
|
Yes
|
Display Device
|
LCD
|
I / P & O / P voltage & frequency, battery voltage, battery capacity, load, fault code
|
|
LED
|
The operation state of UPS
|
|
Alarm
|
battery mode, overload, fault
|
Warning Devices
|
Two ways of alerting: BUZZER sound, lamp signal,
|
Communication Interface
|
SNMP,RS232, AS400, RS485, Service, EPO, BAT temperature compensation, Intelligent Slot
|
Operation
|
Temperature
|
0-40°C
|
Environment
|
Humidity
|
<95% (non condesing)
|
Weight
|
Net weight (include transformer)
|
114Kg / 314Kg
|
|
ross weight (include transformer)
|
164Kg / 364Kg
|
Size W*D*H(mm) UPS machine
|
710 x 470 x 1150
|
APPLICATION:
EX33 high frequency Online UPS is applicable to small and medium-sized data centers, network management center, computer rooms for enterprises, or able to provide solutions to conditions like voltage instantaneous drop-off or damping concussion, high-voltage pulse, voltage pulsation, surge voltage, harmonic distortion, and frequency fluctuation.
Each single phase of the EX33 series UPS is converted to DC through an individual PFC circuit and then transferred to AC through Inverter for output. At the same time, a separate controller is provided for the real time control and data collection of PFC circuit so that the whole system can operate more harmonious or feedback the system state to the customer more promptly. In addition, the controlling of battery charging can extend the battery’s serve lifetime effectively and the twin-channel line input improves the system’s reliability.
Furthermore, the series product is enhanced with excellent performance in protection level, which ensures the stability of UPS working in industrial environment with large dusts.
KEY FEATURES:
Excellent performance in industrial environment protection
Just with the standard product, IP21 protection level (protecting the machine from the intrusion of solid material with the diameter larger than 12mm or the water drops) is achieved. If a higher protection level is required, the optional dust-proof accessories can help to increase the protection level in industrial environment and safeguard the UPS’s security of operation in bad environment.
N+X parallel redundancy (compatible to battery share in the parallel mode)
The maximum of the inbuilt parallel mode is 8 UPS without any other external accessories, which helps the customer to extend the system capacity with low cost. N stands for the minimum amount of UPS in the load and X stands for the amount of redundant UPS in the system. The bigger the number of X is, the higher the reliability of the system.
The advanced controlling strategy is adopted to save the customer’s investment by sharing a battery unit in the parallel redundancy mode.
Intelligent management of battery charging and discharging
The CPU- controlled advanced intelligent charging of battery enables the UPS’s charger to rectify the charging parameter, and provide the optimum charging modes in the answer to the environment, types and amounts of cells, and the using condition of the battery. The scientific charging mode extends the battery’s service lifetime. The optional addition to charging units shortens the time duration for the battery units recharging.
Frontal-board operation and maintenance
The full consideration of customer’s efficiency in using the UPS is embodied in the module design and frontal-board maintenance, which saves time for repairing and improves the machine’s usability.
Twin-channel line input
The UPS provides customer security in power supply with intelligent choice between two-line input and one-line input according to the actual condition.
Remote monitoring
Communication interfaces like RS232/RS485, Intelligent Slot are provided and CMC, WebPower cards of ZLPOWER Company are available for the realization of remote management and monitoring. In addition, the optional AS400 card is suitable for the connection of stem point, which enriches the customer’s choice out of the monitoring demand.
High-efficient DSP chip
The digital Ti DSP controlling chip provides precise data processing capability with excellent performance in output and reliability.
Outstanding electric property
The efficiency of the machines is as high as 93% and reaches over 98% in the ECO mode, which can help to reduce the power loss of UPS.
The EX33 series UPS is designed to China’s power grid with a broader range of input voltage from 210VAC to 475VAC, which ensures that it can be applicable in the awful grid environment or different power supple equipment like generator with its extraordinary input frequency.
The factor that the technology of IGBT FM intelligent rectifier and inverter is used , the input power factor is as high as 0.99, and the input current harmonic wave is as low as 3% makes the output voltage electric property more extraordinary.
Powerful overload capacity: the UPS can work normally under the condition of 110-125% load to 10 minutes, and 1 minute in the condition of ;125-150 load. It also has the output short protection capability.
Flexible arrangement
Flexiblebatteryarrangement of the amount of accumulators in each battery (32, 30, or 28) can be achieved through the parameter resetting in the Industry EX33 series UPS, which effectively solves the question that the damage of some individual cell may influence the life of the whole unit by eliminating the damaged ones from the unit in the process of using UPS