UPS ZLPOWER True Online (P/No: EX2K) series hight frequency online UPS  Is specially designed for serverrs, datacenter critical network devices, sensitive  electronic  equipment, telecom, bank, hospital, bureau, traffic, public security,  ATM and so on.
Features:
* Lanrge Blue Ground LCD digital display shows . Detail Real – Time UPS Status and parameters.
*Set output voltage, Frequency parameter and Bypass function on the display.
*Advanced MCU microprocssor control Technology, ensure long life reliability.
* Excellent Protection against over voltage, Overload, over current, overcharge and so on.
* Input L and N lines reverse wiring detecion.
* DC start function, input PFC revises function.
* Humanized bypass output adjustable.
* RS232/RS485 Intelligent communication monitoring.
* AS-400 Dry contact and SNMP card remote Intelligent control.
* Strong anti – jamming capability.
* Available to work with generators.
* Lightning, surge, short-circuit, nework/fax/ Modem surge protection.
 
| Online UPS MODEL | EX2K | 
| Technology | True Online Double ConversionAdvanced MCU micro-processor control technology, ensure longlift reliabily
 | 
| CAPACITY | VA/W | 2KVA | 
| INPUT | Nominal Voltage |  100/110/115/120VAC or 200/220/230/240VAC | 
| Voltage Range | 60-138VAC or 110-300VAC | 
| Frequency Range | 50Hz/ 60Hz | 
| Phase | Single phase with Ground | 
| Power Factor | >=0.97 | 
| OUTPUT | Voltage | 100/110/115/120* (1±2%)VAC or 200/220/230/240* (1±2%)VAC | 
| Frequency | 50/60Hz(Adjustable) | 
| 50/60Hz(adjustable) 50Hz AC mode; Follow AC mode (AC range 46-54Hz); Battery mode; 50Hz (1±0.2%)  | 
| 60 Hz AC mode ±0,2Hz(Battery mode); Follow AC mode (AC range 56-64Hz); Battery mode; 60Hz (1±0.2%) | 
| Wave Form | Pure Sine Wave | 
| Power Factor | 0.8 or 0.9 | 
| Current Crest Ratio | 3:1 | 
| Overload Capacity | 110%-150% for 30s , over 150% for 200ms | 
| Harmonic Distortion |  < = 3% THD (Linear Load); < = 7% THD (NoLinear Load) | 
| Connections | 03 Multi perpose Socket  | 
| Efficiency | To AC Mode | 85% | 
| To Battery Mode | 83% | 
| Battery ZLPOWER | Type | Sealed free maintenance lead acid battery | 
| Nominal DC voltage | Built in batteries 12V7AH | 
| Quantity | 8pcs | 
| Back-up Time  | >= 12 minutes ( half load)             >= 06 minutes (Full load) | 
| Recharge Time | 5 hours to 90% of capacity full discharge | 
| Charge current(MAX) | 1.0A | 
| Charge voltage | 110V/±0.6V | 
| Bypass | Automatic Transfer | On overload and UPS failure | 
| Before UPS Power-on | Default”ON” user adjustable to “YES” | 
| Transfer Time | 0ms, less than 4ms from inverter to bypass and vice versa | 
| Indicators | LCD Display | UPS status, Battery capacity, Loading, Fault code (LCD: I/P & O/P voltage & frequency, Battery voltage,  | 
| Audible Alarm | Bypass, On battery mode, Battery low, Overload, Fault | 
| Acoustic noise | At 1 meter distance | < 50dB                                 | 
| Communications | Intelligent RS232 serial port | Software support Windows family software, Linux, Sun network operating system, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX, and MAC | 
| SNMP (Optional) | Remove control UPS through SNMP management and Internet | 
| RS485, USB (Optional) | Windows family software and Mac OS | 
| Network Surge Protection | RJ45 I/O port available for network or FAX/Telephone line/Modem | 
| Environmental | Operating Temperature | 0~40  | 
| Operating Humidity | 20~90% ( Non Condensing) | 
| Weight | Net weight (kgs) | 26.5 kg | 
| UPS Dimension | L*W*H (mm) | 455*195*340                                   | 
* Product specifications are subject to change without further notice.