ZLPOWER RM series high frequency Rack mount online UPS is specially designed for servers, data-center critical network devices, sensitive electronic equipment, telecom, bank, hospital, bureau, traffic, public security, ATM and so on.
Features:
*Output voltage, frequency parameter and bypass function can be set via the LCD display.
*LED +LCD display Detailed Real-Time UPS Status and parameters.
*True online double conversion technology with advanced microprocessor control
*Advanced MCU microprocessor control technology, ensure long life reliability.
*Rack mount 19”design to save space
*Excellent Protection against over voltage, over load, over current, over charge and so on.
*Input L and N lines reverse wiring detection, Auto start when AC back.
*DC start function, Input PFC revise function.
*Smart RS232 communication with monitoring software.
*Intelligent slot available for AS-400 Dry contact and SNMP card Remote control.
*Rack mount battery pack to extend backup time.
Model
|
RM6K-C
|
RM6KL-C
|
RM10K-C
|
RM10KL-C
|
Rated Power
|
KVA
|
6KVA
|
6KVA
|
10KVA
|
10KVA
|
Input
|
Phase
|
Single Phase with Ground
|
Nominal Voltage
|
220/230/240Vac
|
Voltage Range
|
176 ~ 276VAC
|
Frequency Range
|
46 ~ 54Hz
|
Power Factor
|
0.98
|
Connection
|
Terminal Block
|
Output
|
Phase
|
Single Phase
|
Voltage
|
110/115/120Vac or 220/230/240VAC ± 1%
|
Frequency
|
46~54Hz (Line mode)
|
50Hz ± 0.05Hz ( Battery mode)
|
Waveform
|
Pure Sine Wave
|
Overload Capability
|
105% ~ 130% for 10 min.,130% for 1 min.
|
Power Factor
|
0.8 or 0.9
|
Connections
|
IEC320-10A * 4 and Terminal Block
|
Bypass
|
Automatic Transfer
|
on overload and UPS failure
|
Before UPS Power-on
|
Yes
|
Voltage Range
|
176 ~ 261VAC
|
Transfer Time
|
Zero
|
LED indicators
|
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault
|
Audible Alarm
|
Bypass, On battery mode, Battery low, Overload, Fault
|
Communications
|
RS-232 Serial Interface
|
Intelligent Slot;
|
OPTIONS: WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC)
|
Network Surge Protection
|
RJ45 I/O port available for network or Fax/Modem
|
Environmental
|
Operating Temperature
|
0 ~ 40°C
|
Operating Humidity
|
20 ~ 90% non-condensing
|
Main Unit
|
Net Weight (Kg)
|
17.70
|
18.30
|
19.70
|
20.30
|
Dimensions
(LxWxH) mm
|
484*653*134
(3U)
|
Battery Pack
|
Type
|
External Battery Pack
|
Nominal DC Voltage
|
192VDC
|
Battery Numbers & Capacity
|
16pcs*12V 7AH
|
External Battery Pack
|
16pcs*12V 7AH
|
External Battery Pack
|
Backup Time
(Full load)
|
4 min
|
Depending on the capacity of external battery packs
|
3 min
|
Depending on the capacity of external battery packs
|
Recharge Time
|
5hrs to 90%
|
5hrs to 90%
|
Charging Current (Max.)
|
2A
|
5A/7A±1A
|
2A
|
5A/7A±1A
|
Charging Voltage
|
219.50VDC±1%
|
Net Weight (Kg)
|
44.50
|
---
|
44.50
|
---
|
Dimensions
(LxWxH) mm
|
484*621*134 (3U)
|
---
|
484*582*134 (3U)
|
-
|